VAST says petabyte SSDs will outgrow today’s parallel file system RAID
Built from 15 TB drives, VAST’s 900 PB system would draw about 5.6 MW instead of 400 kW.
When you purchase through links on our site, we may earn an affiliate commission. Here’s how it works.
VAST Data says petabyte SSDs will outgrow RAID in today’s parallel file systems, according to a simulation of its own 900 PB system that puts the odds of data loss at 1 in 11 over 10 years. At Supercomputing 2026 (SC26), the company explains how.
Bigger drives take longer to rebuild after a failure, leaving more time for further failures to lose data, but operators will still want those large drives because many sites are power-constrained and storage power scales with bandwidth rather than capacity. VAST’s recommended fix: system-wide erasure coding with at least three parity strips.
The company’s principal technical strategist, Glenn Lockwood, walked through the simulation, described as a “discrete event simulation” using real failure data, in an Exhibitor Forum talk during SC26’s HPC System Hardware and Architecture session. With petabyte-scale SSDs swapped in, enclosure-local declustered RAID — the approach used by DDN EXAScaler and HPE Cray ClusterStor, per Lockwood — has those exceptionally high odds of data loss. With global declustering and extra parity, operators can get this down to 1 in 54 million, a significant improvement, but VAST’s own scheme gets to about 1 in 62 billion, three orders of magnitude better.
Lockwood’s case for petabyte SSDs rests on how storage power scales: at about 28 W per SSD, regardless of capacity and including its share of the surrounding infrastructure, plus 20 W per GB/s of bandwidth. Getting 900 PB of flash from 15 TB SSDs would take more than 63K drives, each adding its own bandwidth, for 190 TB/s at 5.6 MW, or “the equivalent of 3,100 or so of Blackwell Ultra GPUs.” Lockwood says, though, that “real AI applications in our experience have never approached needing anything close to that level of performance” from the storage.
With 122 TB drives, at almost an 8K count and much lower 8 TB/s of aggregate bandwidth, the power draw is less than a tenth of that, at about 400 kW. Within that budget, 15 TB SSDs top out at about 250 PB, even with no power left for performance. That power could be better spent on compute and, anyway, 245 TB-class drives are already arriving, with much larger drives expected.
Everything is a series of trade-offs, though, and larger drives come with their own caveats. Lockwood acknowledges the usual reaction to a 245 TB drive: that it’s “a big blast radius,” since a single failure leaves much more to rebuild. And it does take longer: at the same per-drive speed, a 122 TB drive takes twice as long to rebuild as a 60 TB drive, leaving a longer window in which a second failure in a traditional RAID 5 set loses data. Per-drive capacity is potentially outpacing bandwidth increases and, at least within a generation, “the performance of each individual drive does not change,” so this is something that must be accepted or overcome.
The simulated system involves 7,920 SSDs at 122 TB each, using 180 enclosures with 44 drives each. With a RAID 5 single parity solution, there is a 100% chance of data loss over 10 years, but “no one uses single parity anymore.” Double parity still has 1 in 150 odds of data loss over a decade and is considered “state of the art for many open source file systems,” and he explicitly names Lustre and BeeGFS within this context.
For proprietary parallel file system implementations, declustered RAID within an enclosure is the state of the art, instead. Declustered RAID spreads each drive group’s data, parity, and spare space over more drives than usual, allowing for faster rebuilds. Keeping it within an enclosure means that the spread still stays within a single box of drives. Swapping petabyte SSDs into that enclosure-level declustering is what gets to the headline 1 in 11 odds of data loss.